Decree No. 1070824174 issued by the Ministry of the Interior on 17 December 2018 for the interpretive rule pursuant to Subparagraph 6 of Article 33 and Subparagraph 7 of Article 41 of the Public Hazardous Substances and Flammable Pressurized Gases Establishment Standards and Safety Control Regulations

Made 2018-12-17 · Text as of 2026-10-01

Public law and official guidance, published as research. Not legal, tax or financial advice.

About this law

Original title
內政部令2018年12 月17 日內授消字第 1070824174 號核釋「公共危險物品及可燃性高壓氣體設置標準暨安全管理辦法」第33條第6款及第41條第7款「通氣管」之設置規定疑義.
Language
Chinese
Kind
Regulation
Country
Taiwan
Subjects
Waste and hazardous substances
Keywords
hazardous substances

Where to read it

    No source link is recorded for this law.

Text

The law's own text, section by section, as held. Each section has its own link.

  1. 內政部 令 中華民國 107 年 12 月 17 日 內授消字第 1070824174 號 核釋「公共危險物品及可燃性高壓氣體設置標準暨安全管理辦法」第三十三條 第六款及第四十一條第七款「通氣管」之設置規定疑義,並自即日起生效。 一、查儲槽設置之通氣管,係為調整非壓力儲槽內外壓差而設置之必要安全設 備,與通風、排出設備及防止可燃性蒸氣滯留措施等設置目的並不相同,故不 得以前述設備或措施取代通氣管之設置方式。 二、室內儲槽儲存第四類公共危險物品時,設置之通氣管型式應為無閥通氣 管,且需考量可燃性蒸氣自無閥通氣管排出可能造成之危害,故應能排出至建 築物外部一定高度,並距離開口一定距離,以強化場所安全。經參考現行排出 設備規定及日本危險物規制規則規範,無閥通氣管應能將可燃性蒸氣有效排出 至建築物外距地面四公尺以上高處,並距離建築物開口一公尺以上;但儲存高 閃火點物品且其操作溫度未滿攝氏一百度者,因其危險性較低,無閥通氣管之 前端得設置於儲槽專用室內。 三、地下儲槽設置之通氣管,亦應能將可燃性蒸氣有效排出至戶外距地面四公 尺以上高處,並距離建築物開口一公尺以上。 部長 徐國勇

Decree No. 1070824174 issued by the Ministry of the Interior on 17 December 2018 for the interpretive rule pursuant to Subparagraph 6 of Article 33 and Subparagraph 7 of Article 41 of the Public Hazardous Substances and Flammable Pressurized Gases Establishment Standards and Safety Control Regulations · Nelum